Backflow assembly test: Riverside Dental
ApprovedFiled Aug 14, 2024 by Casey Whitcomb, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Aug 14, 2024
- Assembly type
- RP
- Serial number
- A957460
- Size
- 1 1/2
- Test gauge serial
- G-6835
- Gauge calibration date
- Feb 18, 2024
- Check valve 1
- 7.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Relief valve opened at
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Casey Whitcomb, current on the service date
- All required fields present
- Address matches parcel 073-36-01174
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
5094 Turkey Hill Rd
Owner: Marsh Holdings LLC
Parcel 073-36-01174