Back to the backflow review queue

Backflow assembly test: 6688 Ridgeview Trl

Approved

Filed Jun 9, 2026 by Morgan Marsh, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 9, 2026
Assembly type
DC
Serial number
A921487
Size
1
Test gauge serial
G-8617
Gauge calibration date
Feb 14, 2026
Check valve 1
3.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Marsh, current on the service date
  • All required fields present
  • Address matches parcel 073-93-01113
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6688 Ridgeview Trl
Owner: Rowan Harlow
Parcel 073-93-01113