Backflow assembly test: 1941 Meadow Lark Rd

Approved

Filed Dec 11, 2024 by Casey Whitcomb, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Dec 11, 2024
Assembly type
DC
Serial number
A138385
Size
3/4
Test gauge serial
G-3593
Gauge calibration date
Jun 1, 2024
Check valve 1
7.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 073-73-01222
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1941 Meadow Lark Rd
Owner: Drew Danner
Parcel 073-73-01222