Backflow assembly test: 1922 Mill Creek Ln

Approved

Filed Sep 28, 2024 by Morgan Marsh, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 28, 2024
Assembly type
DC
Serial number
K309481
Size
1
Test gauge serial
G-7538
Gauge calibration date
Jun 14, 2024
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Marsh, current on the service date
  • All required fields present
  • Address matches parcel 073-79-01257
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1922 Mill Creek Ln
Owner: Riley Nguyen
Parcel 073-79-01257