Back to the backflow review queue
Backflow assembly test: 6536 Laurel Trl
ApprovedFiled Mar 9, 2026 by Alex Benton, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Mar 9, 2026
- Assembly type
- RP
- Serial number
- B674457
- Size
- 3/4
- Test gauge serial
- G-4683
- Gauge calibration date
- Jul 9, 2025
- Check valve 1
- 3.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.2 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Alex Benton, current on the service date
- All required fields present
- Address matches parcel 073-91-01003
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
6536 Laurel Trl
Owner: Taylor Vance
Parcel 073-91-01003