Back to the backflow review queue

Backflow assembly test: 8300 Sycamore Ln

Approved

Filed Jan 17, 2025 by Alex Benton, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jan 17, 2025
Assembly type
DC
Serial number
A111059
Size
1
Test gauge serial
G-6473
Gauge calibration date
May 28, 2024
Check valve 1
4.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Benton, current on the service date
  • All required fields present
  • Address matches parcel 073-97-01235
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8300 Sycamore Ln
Owner: Morgan Hollins
Parcel 073-97-01235