Backflow assembly test: 5046 Old Church Ln

Approved

Filed May 21, 2026 by Morgan Marsh, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 21, 2026
Assembly type
DC
Serial number
A540717
Size
1
Test gauge serial
G-1675
Gauge calibration date
Jan 20, 2026
Check valve 1
7.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Marsh, current on the service date
  • All required fields present
  • Address matches parcel 073-68-01230
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

5046 Old Church Ln
Owner: Sam Wexler
Parcel 073-68-01230