Backflow assembly test: 2772 Fox Run Way

Approved

Filed Nov 5, 2026 by Taylor Vance, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Nov 5, 2026
Assembly type
RP
Serial number
Z426453
Size
3/4
Test gauge serial
G-3169
Gauge calibration date
Aug 17, 2026
Check valve 1
4.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Vance, current on the service date
  • All required fields present
  • Address matches parcel 005-70-01244
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2772 Fox Run Way
Owner: Casey Stroud
Parcel 005-70-01244