Backflow assembly test: 6239 Ridgeview Trl
ApprovedFiled Dec 26, 2024 by Taylor Benton, Ridge Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Dec 26, 2024
- Assembly type
- RP
- Serial number
- W561993
- Size
- 1
- Test gauge serial
- G-1583
- Gauge calibration date
- Oct 27, 2024
- Check valve 1
- 4.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.6 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Taylor Benton, current on the service date
- All required fields present
- Address matches parcel 005-76-01354
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
6239 Ridgeview Trl
Owner: Jordan Ellery
Parcel 005-76-01354