Backflow assembly test: Main Street Apartments
ApprovedFiled Sep 11, 2026 by Taylor Vance, Northstar Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Sep 11, 2026
- Assembly type
- RP
- Serial number
- B407138
- Size
- 1 1/2
- Test gauge serial
- G-9311
- Gauge calibration date
- May 7, 2026
- Check valve 1
- 4.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.4 psid
- Relief valve opened at
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Taylor Vance, current on the service date
- All required fields present
- Address matches parcel 005-19-01116
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
1462 Orchard Dr
Owner: Wexler Holdings LLC
Parcel 005-19-01116