Back to the backflow review queue

Backflow assembly test: 4350 Sycamore Trl

Approved

Filed Oct 7, 2026 by Hayden Stroud, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Oct 7, 2026
Assembly type
RP
Serial number
W133058
Size
3/4
Test gauge serial
G-4660
Gauge calibration date
Aug 13, 2026
Check valve 1
8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Stroud, current on the service date
  • All required fields present
  • Address matches parcel 005-18-01262
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4350 Sycamore Trl
Owner: Riley Vance
Parcel 005-18-01262