Backflow assembly test: 9019 Mill Creek Trl

Approved

Filed Mar 23, 2026 by Taylor Benton, Ridge Plumbing & Backflow. Filed from a phone.

Report

Date of service
Mar 23, 2026
Assembly type
RP
Serial number
B434285
Size
1
Test gauge serial
G-4092
Gauge calibration date
Jun 6, 2025
Check valve 1
3.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
1.2 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Benton, current on the service date
  • All required fields present
  • Address matches parcel 005-30-01021
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9019 Mill Creek Trl
Owner: Jordan Brandt
Parcel 005-30-01021