Backflow assembly test: 460 Orchard Rd

Approved

Filed Sep 27, 2026 by Taylor Benton, Ridge Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 27, 2026
Assembly type
RP
Serial number
A656179
Size
3/4
Test gauge serial
G-5629
Gauge calibration date
Dec 2, 2025
Check valve 1
6.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Benton, current on the service date
  • All required fields present
  • Address matches parcel 005-92-01184
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

460 Orchard Rd
Owner: Cameron Vance
Parcel 005-92-01184