Back to the backflow review queue

Backflow assembly test: 7193 Hickory Rd

Approved

Filed Oct 17, 2024 by Taylor Benton, Ridge Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 17, 2024
Assembly type
DC
Serial number
W951276
Size
3/4
Test gauge serial
G-4255
Gauge calibration date
Mar 29, 2024
Check valve 1
4.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Benton, current on the service date
  • All required fields present
  • Address matches parcel 005-92-01199
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

7193 Hickory Rd
Owner: Parker Ramirez
Parcel 005-92-01199