Backflow assembly test: 7193 Hickory Rd

Approved

Filed Oct 28, 2025 by Taylor Benton, Ridge Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 28, 2025
Assembly type
DC
Serial number
W951276
Size
3/4
Test gauge serial
G-9127
Gauge calibration date
Aug 16, 2024
Check valve 1
3.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Benton, current on the service date
  • All required fields present
  • Address matches parcel 005-92-01199
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7193 Hickory Rd
Owner: Parker Ramirez
Parcel 005-92-01199