Backflow assembly test: 7587 Meadow Lark Trl
ApprovedFiled Mar 12, 2026 by Taylor Vance, Northstar Backflow Testing. Filed from a phone.
Report
- Date of service
- Mar 12, 2026
- Assembly type
- RP
- Serial number
- A191135
- Size
- 3/4
- Test gauge serial
- G-6004
- Gauge calibration date
- Jun 3, 2025
- Check valve 1
- 3.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.2 psid
- Relief valve opened at
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Taylor Vance, current on the service date
- All required fields present
- Address matches parcel 005-82-01092
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
7587 Meadow Lark Trl
Owner: Quinn Danner
Parcel 005-82-01092