Back to the backflow review queue
Backflow assembly test: Maple Leaf Apartments
Needs reviewFiled Nov 18, 2026 by Drew Stroud, Keystone Backflow Testing. Filed from a phone.
Report
- Date of service
- Nov 18, 2026
- Assembly type
- RP
- Serial number
- W921237
- Size
- 2
- Test gauge serial
- G-8038
- Gauge calibration date
- Jun 14, 2026
- Check valve 1
- 7.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.5 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Stroud, current on the service date
- All required fields present
- Address matches parcel 005-61-01302
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
6254 Quarry Rd
Owner: Benton Holdings LLC
Parcel 005-61-01302