Back to the backflow review queue

Backflow assembly test: 5955 Fox Run Trl

Approved

Filed Sep 21, 2026 by Taylor Benton, Ridge Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Sep 21, 2026
Assembly type
RP
Serial number
A321879
Size
1
Test gauge serial
G-1805
Gauge calibration date
Jul 19, 2026
Check valve 1
6.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Benton, current on the service date
  • All required fields present
  • Address matches parcel 005-25-01338
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

5955 Fox Run Trl
Owner: Hayden Vance
Parcel 005-25-01338