Backflow assembly test: Station Pizza

Approved

Filed Nov 22, 2023 by Cameron Okafor, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Nov 22, 2023
Assembly type
RP
Serial number
W788307
Size
1
Test gauge serial
G-6433
Gauge calibration date
Mar 17, 2023
Check valve 1
5.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Okafor, current on the service date
  • All required fields present
  • Address matches parcel 005-17-01327
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3015 Old Church Rd
Owner: Ellery Holdings LLC
Parcel 005-17-01327