Back to the backflow review queue

Backflow assembly test: Station Pizza

Approved

Filed Nov 17, 2024 by Taylor Benton, Ridge Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 17, 2024
Assembly type
RP
Serial number
W788307
Size
1
Test gauge serial
G-2398
Gauge calibration date
May 22, 2024
Check valve 1
4.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Benton, current on the service date
  • All required fields present
  • Address matches parcel 005-17-01327
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

3015 Old Church Rd
Owner: Ellery Holdings LLC
Parcel 005-17-01327