Backflow assembly test: Maple Leaf Medical Offices

Approved

Filed Jun 21, 2026 by Drew Stroud, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Jun 21, 2026
Assembly type
DC
Serial number
W465856
Size
1 1/2
Test gauge serial
G-7194
Gauge calibration date
Oct 27, 2025
Check valve 1
4.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Stroud, current on the service date
  • All required fields present
  • Address matches parcel 005-71-01296
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4183 Hickory Trl
Owner: Kessler Holdings LLC
Parcel 005-71-01296