Back to the backflow review queue

Backflow assembly test: 3021 Mill Creek Ct

Approved

Filed Jan 4, 2024 by Hayden Stroud, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Jan 4, 2024
Assembly type
RP
Serial number
Z892740
Size
1
Test gauge serial
G-8421
Gauge calibration date
Jul 14, 2023
Check valve 1
5.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Stroud, current on the service date
  • All required fields present
  • Address matches parcel 005-50-01320
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3021 Mill Creek Ct
Owner: Morgan Fairley
Parcel 005-50-01320