Backflow assembly test: 2993 Old Church Rd

Approved

Filed Oct 1, 2026 by Taylor Benton, Ridge Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Oct 1, 2026
Assembly type
RP
Serial number
Z664293
Size
3/4
Test gauge serial
G-4841
Gauge calibration date
Feb 22, 2026
Check valve 1
6.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Benton, current on the service date
  • All required fields present
  • Address matches parcel 005-63-01274
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.