Backflow assembly test: 2156 Spring Branch Ln

Approved

Filed Aug 12, 2025 by Taylor Vance, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Aug 12, 2025
Assembly type
RP
Serial number
Z454297
Size
3/4
Test gauge serial
G-3505
Gauge calibration date
Jun 10, 2025
Check valve 1
7.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Vance, current on the service date
  • All required fields present
  • Address matches parcel 005-42-01148
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2156 Spring Branch Ln
Owner: Jordan Ashby
Parcel 005-42-01148