Backflow assembly test: 3037 Ridgeview Trl

Approved

Filed Oct 26, 2025 by Logan Benton, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 26, 2025
Assembly type
RP
Serial number
Z121745
Size
3/4
Test gauge serial
G-1875
Gauge calibration date
Mar 22, 2025
Check valve 1
7.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Benton, current on the service date
  • All required fields present
  • Address matches parcel 013-19-01102
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.