Backflow assembly test: 8289 Ridgeview Ct

Approved

Filed Oct 18, 2024 by Logan Benton, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 18, 2024
Assembly type
RP
Serial number
Z312766
Size
3/4
Test gauge serial
G-5658
Gauge calibration date
Dec 26, 2023
Check valve 1
3.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Benton, current on the service date
  • All required fields present
  • Address matches parcel 013-85-01090
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.