Backflow assembly test: 4680 Spring Branch Ct
ApprovedFiled Feb 29, 2024 by Logan Benton, Patriot Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Feb 29, 2024
- Assembly type
- DC
- Serial number
- Z685198
- Size
- 1
- Test gauge serial
- G-9515
- Gauge calibration date
- Nov 8, 2023
- Check valve 1
- 7.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Logan Benton, current on the service date
- All required fields present
- Address matches parcel 013-22-01108
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.