Backflow assembly test: 1805 Meadow Lark Trl
ApprovedFiled Dec 16, 2024 by Logan Benton, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Dec 16, 2024
- Assembly type
- RP
- Serial number
- Z882336
- Size
- 1
- Test gauge serial
- G-3195
- Gauge calibration date
- Jul 11, 2024
- Check valve 1
- 0.5 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.2 psid
- Relief valve opened at
- 3.6 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Logan Benton, current on the service date
- All required fields present
- Address matches parcel 013-39-01338
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
1805 Meadow Lark Trl
Owner: Cameron Danner
Parcel 013-39-01338