Backflow assembly test: 1805 Meadow Lark Trl
ApprovedFiled Dec 9, 2025 by Hayden Danner, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Dec 9, 2025
- Assembly type
- RP
- Serial number
- Z882336
- Size
- 1
- Test gauge serial
- G-3962
- Gauge calibration date
- Jun 24, 2025
- Check valve 1
- 9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Relief valve opened at
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Danner, current on the service date
- All required fields present
- Address matches parcel 013-39-01338
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.