Backflow assembly test: 7171 Hickory Way

Approved

Filed Nov 1, 2025 by Jamie Harlow, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 1, 2025
Assembly type
DC
Serial number
A700707
Size
3/4
Test gauge serial
G-8627
Gauge calibration date
Aug 4, 2025
Check valve 1
7.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Harlow, current on the service date
  • All required fields present
  • Address matches parcel 013-45-01265
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.