Back to the backflow review queue

Backflow assembly test: 7986 Quarry Rd

Approved

Filed Aug 17, 2025 by Jamie Harlow, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Aug 17, 2025
Assembly type
RP
Serial number
W637377
Size
3/4
Test gauge serial
G-4755
Gauge calibration date
May 11, 2024
Check valve 1
3.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
1.8 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Harlow, current on the service date
  • All required fields present
  • Address matches parcel 013-85-01328
  • RP relief valve must open at 2.0 psid or more.
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7986 Quarry Rd
Owner: Shawn Harlow
Parcel 013-85-01328