Back to the backflow review queue

Backflow assembly test: 2428 Mill Creek Dr

Approved

Filed Dec 11, 2024 by Jamie Harlow, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Dec 11, 2024
Assembly type
RP
Serial number
A371829
Size
1
Test gauge serial
G-1110
Gauge calibration date
Aug 20, 2024
Check valve 1
7.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Harlow, current on the service date
  • All required fields present
  • Address matches parcel 013-90-01139
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2428 Mill Creek Dr
Owner: Jordan Ellery
Parcel 013-90-01139