Back to the backflow review queue

Backflow assembly test: 8798 Cedar Hollow Way

Approved

Filed Nov 19, 2025 by Jamie Harlow, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 19, 2025
Assembly type
RP
Serial number
A665287
Size
1
Test gauge serial
G-3529
Gauge calibration date
Feb 9, 2025
Check valve 1
6.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Harlow, current on the service date
  • All required fields present
  • Address matches parcel 013-84-01138
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8798 Cedar Hollow Way
Owner: Avery Stroud
Parcel 013-84-01138