Back to the backflow review queue

Backflow assembly test: 9272 Orchard Way

Approved

Filed Sep 14, 2026 by Logan Benton, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 14, 2026
Assembly type
RP
Serial number
K969157
Size
3/4
Test gauge serial
G-5746
Gauge calibration date
Jun 3, 2026
Check valve 1
4.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Benton, current on the service date
  • All required fields present
  • Address matches parcel 013-85-01026
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9272 Orchard Way
Owner: Rowan Hollins
Parcel 013-85-01026