Backflow assembly test: Two Rivers Self Storage
ApprovedFiled Dec 7, 2025 by Hayden Danner, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Dec 7, 2025
- Assembly type
- RP
- Serial number
- K793220
- Size
- 4
- Test gauge serial
- G-7178
- Gauge calibration date
- Sep 26, 2025
- Check valve 1
- 7.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 2.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Danner, current on the service date
- All required fields present
- Address matches parcel 013-73-01147
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
6947 Orchard Ct
Owner: Whitcomb Holdings LLC
Parcel 013-73-01147