Back to the backflow review queue

Backflow assembly test: 712 Cedar Hollow Rd

Approved

Filed Jan 9, 2025 by Riley Kessler, Patriot Backflow Testing. Filed from a phone.

Report

Date of service
Jan 9, 2025
Assembly type
RP
Serial number
A102319
Size
3/4
Test gauge serial
G-8277
Gauge calibration date
Sep 23, 2024
Check valve 1
5.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Kessler, current on the service date
  • All required fields present
  • Address matches parcel 019-91-01085
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

712 Cedar Hollow Rd
Owner: Parker Harlow
Parcel 019-91-01085