Back to the backflow review queue

Backflow assembly test: 9638 Quarry Ln

Approved

Filed Jul 17, 2026 by Morgan Calloway, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jul 17, 2026
Assembly type
DC
Serial number
W228730
Size
1
Test gauge serial
G-8935
Gauge calibration date
Jun 4, 2025
Check valve 1
0.8 psid
Check valve 1 closed tight
No
Check valve 2
2.1 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Calloway, current on the service date
  • All required fields present
  • Address matches parcel 019-23-01042
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9638 Quarry Ln
Owner: Reese Ashby
Parcel 019-23-01042