Back to the backflow review queue

Backflow assembly test: Crossroads Pizza

Approved

Filed Oct 13, 2023 by Morgan Calloway, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 13, 2023
Assembly type
RP
Serial number
W705458
Size
1 1/2
Test gauge serial
G-4266
Gauge calibration date
Aug 27, 2023
Check valve 1
6.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Calloway, current on the service date
  • All required fields present
  • Address matches parcel 019-46-01342
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6888 Hickory Dr
Owner: Pruitt Holdings LLC
Parcel 019-46-01342