Backflow assembly test: Corner Elementary School
ApprovedFiled Jun 26, 2026 by Morgan Calloway, Lakeside Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jun 26, 2026
- Assembly type
- DC
- Serial number
- K710359
- Size
- 2
- Test gauge serial
- G-2370
- Gauge calibration date
- Sep 14, 2025
- Check valve 1
- 3.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.2 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Morgan Calloway, current on the service date
- All required fields present
- Address matches parcel 019-85-01072
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.