Back to the backflow review queue

Backflow assembly test: 4022 Hickory Way

Approved

Filed May 8, 2026 by Taylor Wexler, Lakeside Backflow Testing. Filed from a phone.

Report

Date of service
May 8, 2026
Assembly type
DC
Serial number
Z498520
Size
1
Test gauge serial
G-1034
Gauge calibration date
Aug 28, 2025
Check valve 1
6.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Wexler, current on the service date
  • All required fields present
  • Address matches parcel 019-44-01033
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4022 Hickory Way
Owner: Rowan Hollins
Parcel 019-44-01033