Backflow assembly test: 5014 Turkey Hill Way

Approved

Filed Jul 14, 2026 by Riley Kessler, Patriot Backflow Testing. Filed from a phone.

Report

Date of service
Jul 14, 2026
Assembly type
RP
Serial number
B193845
Size
3/4
Test gauge serial
G-8274
Gauge calibration date
May 15, 2026
Check valve 1
6.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Riley Kessler, current on the service date
  • All required fields present
  • Address matches parcel 019-70-01344
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5014 Turkey Hill Way
Owner: Avery Calloway
Parcel 019-70-01344