Back to the backflow review queue

Backflow assembly test: 4967 Stone Gate Ct

Approved

Filed May 20, 2026 by Logan Vance, Lakeside Backflow Testing. Filed from a phone.

Report

Date of service
May 20, 2026
Assembly type
RP
Serial number
Z344501
Size
3/4
Test gauge serial
G-3850
Gauge calibration date
Oct 17, 2025
Check valve 1
5.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Vance, current on the service date
  • All required fields present
  • Address matches parcel 019-78-01195
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4967 Stone Gate Ct
Owner: Jamie Nguyen
Parcel 019-78-01195