Back to the backflow review queue

Backflow assembly test: 8881 Ridgeview Way

Approved

Filed Feb 15, 2026 by Taylor Wexler, Lakeside Backflow Testing. Filed from a phone.

Report

Date of service
Feb 15, 2026
Assembly type
RP
Serial number
K793960
Size
3/4
Test gauge serial
G-8657
Gauge calibration date
Jul 22, 2025
Check valve 1
5.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Wexler, current on the service date
  • All required fields present
  • Address matches parcel 019-38-01283
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

8881 Ridgeview Way
Owner: Casey Hollins
Parcel 019-38-01283