Back to the backflow review queue

Backflow assembly test: Riverside Self Storage

Approved

Filed Nov 19, 2025 by Hayden Stroud, Patriot Backflow Testing. Filed from a phone.

Report

Date of service
Nov 19, 2025
Assembly type
RP
Serial number
W902764
Size
2
Test gauge serial
G-6487
Gauge calibration date
Aug 13, 2025
Check valve 1
6.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Stroud, current on the service date
  • All required fields present
  • Address matches parcel 019-14-01162
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8018 Laurel Dr
Owner: Stroud Holdings LLC
Parcel 019-14-01162