Back to the backflow review queue
Backflow assembly test: 5914 Meadow Lark Trl
ApprovedFiled Oct 31, 2024 by Morgan Stroud, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 31, 2024
- Assembly type
- DC
- Serial number
- A914280
- Size
- 1
- Test gauge serial
- G-3285
- Gauge calibration date
- Feb 12, 2024
- Check valve 1
- 6.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Morgan Stroud, current on the service date
- All required fields present
- Address matches parcel 021-31-01152
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
5914 Meadow Lark Trl
Owner: Quinn Harlow
Parcel 021-31-01152