Back to the backflow review queue

Backflow assembly test: 8016 Meadow Lark Ct

Approved

Filed Sep 17, 2024 by Drew Stroud, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
Sep 17, 2024
Assembly type
PVB
Serial number
W931547
Size
1
Test gauge serial
G-8655
Gauge calibration date
May 15, 2024
Check valve 1
5.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Stroud, current on the service date
  • All required fields present
  • Address matches parcel 021-45-01258
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

8016 Meadow Lark Ct
Owner: Shawn Kessler
Parcel 021-45-01258