Backflow assembly test: 5221 Cedar Hollow Dr
ApprovedFiled Jan 6, 2025 by Alex Ashby, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jan 6, 2025
- Assembly type
- RP
- Serial number
- A133008
- Size
- 3/4
- Test gauge serial
- G-5144
- Gauge calibration date
- Jul 17, 2024
- Check valve 1
- 8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1 psid
- Relief valve opened at
- 4.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Alex Ashby, current on the service date
- All required fields present
- Address matches parcel 021-90-01163
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
5221 Cedar Hollow Dr
Owner: Avery Okafor
Parcel 021-90-01163