Backflow assembly test: 5576 Old Church Ct

Approved

Filed Mar 29, 2026 by Alex Ashby, Patriot Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Mar 29, 2026
Assembly type
PVB
Serial number
A967951
Size
3/4
Test gauge serial
G-3091
Gauge calibration date
Feb 12, 2026
Check valve 1
3.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Ashby, current on the service date
  • All required fields present
  • Address matches parcel 021-41-01082
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5576 Old Church Ct
Owner: Blake Nguyen
Parcel 021-41-01082