Back to the backflow review queue

Backflow assembly test: 1147 Turkey Hill Trl

Approved

Filed May 1, 2025 by Drew Stroud, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
May 1, 2025
Assembly type
RP
Serial number
Z209478
Size
1
Test gauge serial
G-1807
Gauge calibration date
Dec 18, 2024
Check valve 1
8.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Stroud, current on the service date
  • All required fields present
  • Address matches parcel 021-27-01352
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1147 Turkey Hill Trl
Owner: Emerson Stroud
Parcel 021-27-01352