Backflow assembly test: 1147 Turkey Hill Trl

Approved

Filed May 20, 2026 by Avery Ramirez, Clearwater Backflow Testing. Filed from a phone.

Report

Date of service
May 20, 2026
Assembly type
RP
Serial number
Z209478
Size
1
Test gauge serial
G-9603
Gauge calibration date
Apr 4, 2026
Check valve 1
3.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 021-27-01352
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

1147 Turkey Hill Trl
Owner: Emerson Stroud
Parcel 021-27-01352